Settings
Rows only count if USE is checked. Amps mode uses: amps×volts×mult. Watts mode uses the typed watts.
Demand watts = watts×demand.
Other Loads now exists for: Main House + each Suite. And if you enable 2+ suites, a Shared Loads table appears.
Other Loads now exists for: Main House + each Suite. And if you enable 2+ suites, a Shared Loads table appears.
Main House Basic Load (Your sqft method)
Basement factor • sqm/90 • ceiling to 1000
Total sqft = up + (bsmt × factor) →
sqm = sqft ÷ 10.7639 →
k = sqm ÷ 90 →
basicW = CEILING( 5000 + (k − 1)×1000 , 1000 )
Total sqft for load calc
—
Total sqm
—
sqm ÷ 90
—
Basic load (CEILING to 1000)
—
Suites
Suite 1 is always available. Toggle Suite 2 and Suite 3 when needed.
Change added: Suite 2 & 3 default Range = 6000W (auto-set when enabled / reset / load).
Change added: Each suite has its own Other Loads section with the same 25% rule.
Change added: If 2+ suites are enabled, a Shared Loads section appears.
Change added: Suite 2 & 3 default Range = 6000W (auto-set when enabled / reset / load).
Change added: Each suite has its own Other Loads section with the same 25% rule.
Change added: If 2+ suites are enabled, a Shared Loads section appears.
Main House
Unit Multiplier| USE | Load Name | Mode | Amps | Volts | Mult | Watts | Demand | Demand Watts |
|---|
House Demand (before unit mult)
—
House Amps (after unit mult)
—
Suite 1
Unit Multiplier| USE | Load Name | Mode | Amps | Volts | Mult | Watts | Demand | Demand Watts |
|---|
Suite 1 Demand
—
Suite 1 Amps
—
Other Loads (Main House • your range / no-range 25% rule)
Welder • Compressor • Laser • Wall Oven • etc.
If Range = YES: demand = sum(other) × 0.25
If Range = NO: demand = min(6000, sum(other)) + max(0, sum(other) − 6000) × 0.25
If Range = NO: demand = min(6000, sum(other)) + max(0, sum(other) − 6000) × 0.25
| USE | Device | Mode | Amps | Volts | Mult | Watts | Demand | Demand Watts |
|---|
Other loads sum @100%
—
Other loads demand (after rule)
—
Other Loads (Suite 1)
Same 25% rule • suite-specific| USE | Device | Mode | Amps | Volts | Mult | Watts | Demand | Demand Watts |
|---|
Other loads sum @100%
—
Other loads demand (after rule)
—
Grand Total
Total Demand Watts
—
Total Demand Amps (Default Voltage)
—
Grand Total includes:
House + Suite(s) + Shared (if 2+ suites) + Main House Other + Suite Other(s).